IEC 60502 Standard Three Core Cables

Trè cables core - IEC 60502 Standard

Conduttore: Plain annealed copper or aluminum conductor.
Protezione di u cunduttore: The conductor shielding shall be non-metallic and shall consist of an extruded semi-conductive compound with a semiconductor strip applied on top of the semiconductor compound. The conductor shield is not required for PVC, EPR/HEPR insulated cables in the 1.8/3KV to 3.6/6KV range.
Insulazione: 1.8/3KV and 3.6/6KV cable ranges are generally insulated with PVC, but can also be insulated with XLPE, EPR/HEPR.

Metal/conductor/insulation shield
Adhesives
Armatura (facultativu)

Round Steel Wire Armored Cable Diameter

Virtual Diameter Under Armor Layer (mm)
Diametru di u cable armatu (mm)
>
<
-
10
1.25
10
15
1.25
15
25
1.6
25
35
2.0
35
60
2.5
60
-
3.15

Armor Layer Thickness

Virtual Diameter Under Armor Layer (mm)
Galvanized Steel/Steel (mm)
Aluminum/Aluminum Alloy (mm)
>
<
-
30
0.2
0.5
30
70
0.5
0.5
70
-
0.8
0.8

Physical Properties:

Temperature di funziunamentu: up to 70°C (PVC insulation); finu à 90 ° C (XLPE or EPR insulation)
Gamma di temperatura: -5°C (giacca di PVC); -20°C (giacca PE)
Temperature de court-circuit (maximum duration in case of short-circuit not exceeding 5s): 140-160°C ( guaina PVC ); -40°C ( PE sheath ); -20°C ( PE sheath )
250°C (giacca PE)
Radiu di curvatura: 15 x FROM

Nominal Cross Section (mm2)
Unarmored Cable
Round Steel Wire Armor
Insulation Nominal Thickness (mm)
Copper Strip Thickness (mm)
Copper Wire Shield Area (mm2)
Spessore nominale di a giacca (mm)
AO Diameter (mm)
Approximate Weight (kg/km)
Nominal Pad Thickness (mm)
Armor Thickness (mm)
AO Diameter (mm)
Approximate weight (kg/km)
CU
AL
CU
AL
10
2.0
0.1
16
1.8
23
650
460
1.2
1.6
1.8
28
1480
1290
16
2.0
0.1
16
1.8
24
840
540
1.2
1.6
1.9
29
1720
1410
25
2.0
0.1
16
1.8
26
1160
680
1.2
1.6
1.9
32
2130
1650
35
2.0
0.1
16
1.8
29
1490
820
1.2
2.0
2.1
36
2810
2140
50
2.0
0.1
16
1.9
32
1900
1000
1.2
2.0
2.2
39
3340
2450
...
...
...
...
...
...
...
...
...
...
...
...
...
...

Applicazione:

Three-core cables are designed for power distribution from 3.6/6.6KV to 19/33KV at 50Hz. They are mainly used in a wide range of applications such as power supply stations, conduiti interni, all'aperto, buried and in water, In quantu à l'installazione di i cables à l'industria, Stazioni di Distribuzione, è CABLE DI SALITÀ POWER.

    Per piacè sentite liberu di dà a vostra dumanda in a forma sottu.