IEC 60502 Standard Three Core Cables

Tres cables básicos - IEC 60502 Estándar

Conductor: Conductor simple de cobre ou aluminio recocido.
Conductor shielding: The conductor shielding shall be non-metallic and shall consist of an extruded semi-conductive compound with a semiconductor strip applied on top of the semiconductor compound. The conductor shield is not required for PVC, EPR/HEPR insulated cables in the 1.8/3KV to 3.6/6KV range.
Illamento: 1.8/3As gamas de cables KV e 3,6/6KV están xeralmente illadas con PVC, but can also be insulated with XLPE, EPR/HEPR.

Metal/conductor/insulation shield
Adhesivos
Armor (optional)

Round Steel Wire Armored Cable Diameter

Virtual Diameter Under Armor Layer (mm)
Armored Cable Diameter (mm)
>
<
-
10
1.25
10
15
1.25
15
25
1.6
25
35
2.0
35
60
2.5
60
-
3.15

Armor Layer Thickness

Virtual Diameter Under Armor Layer (mm)
Galvanized Steel/Steel (mm)
Aluminum/Aluminum Alloy (mm)
>
<
-
30
0.2
0.5
30
70
0.5
0.5
70
-
0.8
0.8

Propiedades físicas:

Temperatura de funcionamento: ata 70°C (Illamento de PVC); ata 90°C (Illamento XLPE ou EPR)
Rango de temperatura: -5°C (Chaqueta de PVC); -20°C (Chaqueta PE)
Temperatura de curtocircuíto (maximum duration in case of short-circuit not exceeding 5s): 140-160°C ( Funda de PVC ); -40°C ( PE sheath ); -20°C ( PE sheath )
250°C (Chaqueta PE)
Raio de curvatura: 15 x DESDE

Sección transversal nominal (MM2)
Cable sen blindaxe
Round Steel Wire Armor
Illamento Espesor Nominal (mm)
Espesor da tira de cobre (mm)
Área de blindaxe de fío de cobre (MM2)
Espesor nominal da chaqueta (mm)
Diámetro AO (mm)
Peso aproximado (kg/km)
Espesor nominal da almofada (mm)
Espesor da armadura (mm)
Diámetro AO (mm)
Peso aproximado (kg/km)
CU
Al
CU
Al
10
2.0
0.1
16
1.8
23
650
460
1.2
1.6
1.8
28
1480
1290
16
2.0
0.1
16
1.8
24
840
540
1.2
1.6
1.9
29
1720
1410
25
2.0
0.1
16
1.8
26
1160
680
1.2
1.6
1.9
32
2130
1650
35
2.0
0.1
16
1.8
29
1490
820
1.2
2.0
2.1
36
2810
2140
50
2.0
0.1
16
1.9
32
1900
1000
1.2
2.0
2.2
39
3340
2450
...
...
...
...
...
...
...
...
...
...
...
...
...
...

Aplicación:

Three-core cables are designed for power distribution from 3.6/6.6KV to 19/33KV at 50Hz. They are mainly used in a wide range of applications such as power supply stations, conducións interiores, ao aire libre, buried and in water, así como para a instalación de cables á industria, distribution stations, and power station cables.

    Non dubide en dar a súa consulta no seguinte formulario.


    Subscríbete!