VDE 0276 MV standar 3 Kabel Inti Kab

MV 3 core cables - VDE 0276 Standar

Conductors: Stranded round copper or aluminum conductors according to IEC 60228, VDE 0276 Class 2 / VDE 0295 HD 383.
Conductor shield: Semiconductor composite layer consisting of a non-metallic extruded layer, tightly wrapped with an insulating layer to exclude internal gaps.
Penebat: Extruded XLPE-2XI1 type compound according to DIN VDE 0207 part 22 and HD 620.1.

Jaket njaba PVC / PE / LSZH
PVC/PE/LSZH sarung pamisah (opsional)
Metal/insulation/conductor shield
Adhesive
waja (opsional)

Tingkat voltase:

Tegangan Rated Uo/U
Tegangan operasi (max)
Testing Voltage
3.6/6KV
8KV
12.5KV
6/10KV
12KV
21KV
8.7/15KV
18KV
30.5KV
12/20KV
24KV
42KV
18/30KV
36KV
63KV

Karakteristik Fisik:

Operating temperature: nganti 90 ° C
Temperature range: -5° C (Jaket PVC); -20° C (Jaket PE)
Short-circuit temperature: 250° C (durasi maksimum short-circuit ora ngluwihi 5s)
Bend radius: 15 x saka (non-metallic sheath)
30 x saka (aluminum jacket)

Cable Structure Parameter: Take the example of N2XSEY NA2XSEY

Nominal Cross Section (mm²)
Approximate Conductor OD (mm)
Insulation Nominal Thickness (mm)
Copper Strip Thickness (mm)
Copper Wire Shield Area (mm²)
Approximate Insulation OD (mm)
Nominal Jacket Thickness (mm)
Approximate Outside Diameter (mm)
25
6.05
2.5
0.1
16
12.5
1.5
37
35
7.10
2.5
0.1
16
13.5
1.6
39
50
8.25
2.5
0.1
16
14.7
1.6
42
70
9.90
2.5
0.1
16
16.3
1.7
46
95
11.7
2.5
0.1
16
18.1
1.7
50
120
13.1
2.5
0.1
16
19.5
1.8
53
150
14.3
2.5
0.1
25
20.7
1.8
56
185
16.3
2.5
0.1
25
22.7
1.9
60
...
...
...
...
...
...
...
...

Aplikasi:

Three-core power cables have a voltage range from 3.8/6.6KV to 19/33KV and a frequency of 50Hz, and are mainly used in power supply stations, indoor and outdoor laying, saluran pipa, trowongan, mines, shafts, direct burial in the soil and underwater, lsp., and are able to withstand considerable pressure and mechanical forces, axial tensile force.