BS 6622/BS 7835 Standard Single-Core MV Cables

BS 6622 BS 7835 standard single core medium-voltage power cables

Oludari obinrin: Plain Annealed Copper or Aluminum
Jakeka ita: PVC/PE/LSZH
Igboru sara: XLPE/EPR

Insulation Layer Parameters:

Agbelebu Agbelebu Abala
Thickness of Insulation at Nominal Voltage
3.8/6.6KV (Um=7.2KV)
6.35/11KV (Um=12KV)
8.7/15KV(Um=17.5KV)
12.7/22KV(Um=24KV)
19/33KV(Um=36KV)
mm2
mm
mm
mm
mm
mm
70 185
2.5
3.4
4.5
5.5
8.0
240
2.6
3.4
4.5
5.5
8.0
300
2.8
3.4
4.5
5.5
8.0
400
3.0
3.4
4.5
5.5
8.0
≥500
3.2
3.4
4.5
5.5
8.0

Awọn abuda ti ara:

Operating Temperature: soke si 90 °C
Temperature Range: -5°C (PVC jaketi); -20°C (PE jaketi)
Short-Circuit Temperature: 250°C (o pọju iye akoko kukuru-yika ko koja 5s)
Bending Radius: 12 x LATI

Ti won won Foliteji Uo/U
Ṣiṣẹ Foliteji (Um)
Test Voltage (rms)
3.8/6.6KV
7.2KV
6.35/11KV
12KV
25.5KV
8.7/15KV
17.5KV
35KV
12.7/22KV
24KV
51KV
19/33KV
36KV
76KV

APPLICATION:

The standard power single-core cables have a voltage range from 3.8/6.6KV to 19/33KV and a frequency of 50Hz. they are mainly used in a variety of places such as power supply stations, ile ati ita laying, in pipelines and tunnels, in mines and shafts, in direct burial in the soil and underwater at the bottom of the sea, patako ati bẹbẹ. They are capable of withstanding considerable pressures and mechanical external forces, and axial tensile forces.